Photoelectronic Smoke Detector with
Built-in Wireless Transmitter
Model # 1008-4
INSTALLATION AND
OPERATION MANUAL
Zobrazit stránku 0
1 2 3 4 5 6 ... 27 28

Shrnutí obsahu

Strany 1 - OPERATION MANUAL

1Photoelectronic Smoke Detector with Built-in Wireless TransmitterModel # 1008-4INSTALLATION ANDOPERATION MANUAL

Strany 2

10as no other door or other obstructions block the path of smoke to the detector.• In rooms with sloped, peaked, or gabled ceilings, mount detectors

Strany 3

11This detector will provide maximum protection when installed in compliance with the National Fire Protection Association (NFPA). Standard NFPA 72, h

Strany 4

12exhausts, near furnaces, hot water heaters, or gas space heaters. Install detectors at least 20 feet (6 meters) away from kitchens and any other ar

Strany 5

13• In damp or very humid areas, or next to bathrooms with showers. The moisture in humid air can enter the sensing chamber as water vapor, and will

Strany 6

14General InformationBefore installing detectors, please thoroughly read these installation instructions and NFPA 72, which provides detailed informat

Strany 7

15the detector to automatically maintain proper operation at factory calibrated detection levels, even when sensitivity is altered due to the presence

Strany 8

16Table 1: Detector LED ModesGreen LED Red LED Piezoelectric HornPower-up Blinks every 5 secondsBlinks every 5 secondsOffNormal (standby) Blinks every

Strany 9 - Acceptable location

17once every 5 seconds. When alarm has been activated by smoke, the red LED blinks every 1 second. The LED indication must not be used in place of the

Strany 10 - Horizontal

18Battery Installation and ReplacementTo replace the battery:1. Remove the detector from its mounting base by twisting the detector counterclockwise.

Strany 11

19ProgrammingThe smoke detector is pre-programmed at the factory.Switch SettingsThe Silent Call system is digitally coded. The code sent by the transm

Strany 12 - Incorrect

2What smoke detectors can do:Smoke detectors are designed to provide early warning of developing res at a reasonable cost. They monitor the air and c

Strany 13

20BEFORE PERMANENTLY INSTALLING THE DETECTOR. To check, perform the test described in the TESTING SIGNAL STRENGTH section of this manual. To mount the

Strany 14

21•DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 9.Dust Covers are an effective

Strany 15

22Testing the SensorDetectors must be tested after installation and following periodic maintenance. The Model #1008-4 may be tested as follows:A. Test

Strany 16 - Table 1: Detector LED Modes

23B. Smoke Entry TestHold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the detector until the unit

Strany 17

24Testing Signal StrengthNOTE: Remove battery tab before installation.A test should be performed before installation to determine a strong communicati

Strany 18

25MaintenanceNOTE: Power must be removed from the detector before performing maintenance of any kind by removing the detector’s battery.1. To ensure

Strany 19 - Wireless Smoke Detector

267. Replace the detector cover by placing it over the screen/sensing chamber and turning it clockwise until it snaps into place.8. Reinstall the b

Strany 20

27What to do in case of re• Don’t panic; stay calm. Follow your family escape plan.• Get of the house as quickly as possible. Don’t stop to get dre

Strany 21

28SpecicationsPower Source: One 3-volt CR123A Lithium Battery (included). (Replace with Duracell DL123A, Panasonic CR123A)Height: 2.3 inches (58 mm

Strany 22

3Smoke detectors may not sense res that start where smoke cannot reach the detectors such as in chimneys, in walls, on roofs, or on the other side of

Strany 23 - B. Smoke Entry Test

4can sense every kind of re every time. In general, detectors may not always warn you about red caused by carelessness and safet

Strany 24

5area. See gure 1. Two detectors are required in homes with two bedroom areas. See gure 2.• Put a smoke detector on every level of a multi-level res

Strany 25

6DiningRoomKitchenBedroomBedroomBedroomLiving RoomSmoke detectors for minimum protectionSmoke detectors for more protectionFamilyRoomFigure 2: recomme

Strany 26

7Smoke detectors for minimum protectionSmoke detectors for more protectionBedroomBedroomBedroomLivingRoomKitchenBasementGarageFigure 3: recommended sm

Strany 27

8• Put a smoke detector inside every bedroom where someone sleeps with the door closed. Smoke could be blocked by the closed door, or the alarm may n

Strany 28 - Specications

9Best locationAcceptable locationDeadAirSpaceBest incenter ofceilingNo closer than 4 inch(10 cm) from side wallMount on wall at least 4 inch(10 cm) fr